02(0 X 02) Read The Status Of The Input (Read Di S ) - ICPDAS ECAT-2610 User Manual

Ethercat to modbus rtu gateway
Table of Contents

Advertisement

EtherCAT to Modbus RTU Gateway
02(0x02) Read the Status of the Input (Read DIs)
This function code is used to read the current digital input value.
[Request]
Byte
Description
00
Net ID (Station Number)
01
Function Code
02-03
Starting DI Address
04-05
Number of Points (Channels)
[Response]
Byte
Description
00
Net ID (Station Number)
01
Function Code
02
Byte Count
03
Data
[Error Response]
Byte
Description
00
Net ID (Station Number)
01
Function Code
02
Exception Code
Copyright © 2017 ICP DAS CO., Ltd. All Rights Reserved.
Size
1 Byte
1 to 247
1 Byte
0x02
Refer to the Modbus address depends on your
slave device for more details.
2 Bytes
Byte 02 = high byte
Byte 03 = low byte
Byte 04 = high byte
2 Bytes
Byte 05 = low byte
Size
1 Byte
1 to 247
1 Byte
0x02
Byte Count of Response
1 Byte
( n =(Points+7)/8 )
n= 1; Byte 03 = data bit 7 to 0
n= 2; Byte 04 = data bit 15 to 8
n Bytes
.......
n= m; Byte m+2 = data bit (8m-1) to 8(m-1)
Size
1 Byte
1 to 247
1 Byte
0x82
Refer to the Modbus Standard Specifications for
1 Byte
more details
Value
Value
Value