Figure 12-7 Fault 3: Advanced Link Fault (Taking Rc3000-15 A To Rc3000-15 B For Example); Table 12-16 Fault 3: Advanced Link Fault (Taking Rc3000-15 A To Rc3000-15 B For Example) - Raisecom RC3000-15 Hardware Description

Table of Contents

Advertisement

Raisecom
RC3000-15 (P100R001) Hardware Description
Classification
Teleprotection A
Alarm status
Yellow alarm is
generated.

Figure 12-7 Fault 3: advanced link fault (taking RC3000-15 A to RC3000-15 B for example)

Table 12-16 Fault 3: advanced link fault (taking RC3000-15 A to RC3000-15 B for example)

Classification
Teleprotection A
Service status
Not involved
Alarm status
Not involved
RC3000-15 A
LOS alarm is generated.
The Tx direction to
teleprotection device A
carries Yellow alarm
(Yellow alarm takes bit 1 in
the overhead).
RC3000-15 A
Not involved
Not involved
Raisecom Proprietary and Confidential
Copyright © Raisecom Technology Co., Ltd.
RC3000-15 B
Not involved
RC3000-15 B
The Rx direction to the
advanced link is
disconnected.
Valid data in the Tx
direction to teleprotection
device B is all-1.
The LOS alarm is generated.
12 Telecontrol service cards
Teleprotection B
The "All Ones"
alarm is generated.
Teleprotection B
Valid data in Rx
direction is all-1.
The "All Ones"
alarm is generated.
189