Test Stop Mode 1 - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

7.3.4.2

Test stop mode 1

Test stop mode 1
Figure 7-6
This mode only knows the internal feedback signal (= signal level at the DO terminal) used to
test the F-DO output transistors.
DO+
Step 1
OFF
Step 2
ON
Step 3
OFF
Step 4
ON
Step 5
OFF
Test sequence for test stop mode 1
This monitoring function can be used to verify the ability of the F-DO output transistors to
switch (off) - even if the actuator itself does not provide a feedback signal.
Before testing the F-DOs, the F-DIs are tested by switching off the power supply (L1+, L2+).
The system waits for the parameterized delay time p10001 (SI delay time for test stop)
between the individual test steps before the expected response is checked.
Safety Integrated
Function Manual, (FHS), 11/2009, 6SL3097-4AR00-0BP0
7.3 Commissioning TM54F by means of STARTER/SCOUT
F-DO circuit, test stop mode 1
DO-
Expected response, DIAG signal
OFF
LOW
ON
LOW
ON
LOW
OFF
HIGH
OFF
LOW
Commissioning
135