Parameters for the sub-system, which comprises sub-system elements that must be defined
during the design phase:
● T2: Diagnostic test interval
● β: Susceptibility to common cause failure
● DC: Diagnostic coverage
The PFH
values for subsystems.
The user has the following options when setting up a safety-related controller:
● Use devices and sub-systems that already comply with EN ISO 13849-1:2006, IEC/EN
● Develop own subsystems:
EN 62061 does not include information about non-electric systems. The standard provides
detailed information on implementing safety-related electrical, electronic, and programmable
electronic control systems. EN ISO 13849-1:2006
must be applied for non-electrical systems.
Note
Details of simple sub-systems that have been implemented and integrated are now available
as "functional examples".
Note
IEC 62061 has been ratified as EN 62061 in Europe and harmonized as part of the
Machinery Directive.
Safety Integrated
Function Manual, (FHS), 11/2009, 6SL3097-4AR00-0BP0
value of the safety-related controller is determined by adding the individual PFH
D
61508, or IEC/EN 62061. The standard provides information specifying how qualified
devices can be integrated when safety functions are implemented.
– Programmable, electronic systems and complex systems: Application of EN 61508 or
EN 61800-5-2.
– Simple devices and subsystems: Application of EN 62061.
Standards and regulations
1.2 Safety of machinery in Europe
D
25