Acceptance tests and acceptance reports
9.3 Acceptance tests
No.
STO is initiated after the SS1 delay time expires (p9652, p9852).
No Safety faults and alarms (r0945, r2122, r2132)
•
r9772.0 = r9772.1 = 1 (STO selected and active – CU, via terminals)
•
r9872.0 = r9872.1 = 1 (STO selected and active – MM, via terminals)
•
r9772.2 = r9872.2 = 0 (SS1 inactive – CU and MM, via terminals)
•
r9773.0 = r9773.1 = 1 (STO selected and active – drive, via terminals), r9720/r9722.0
•
r9773.2 = 0 (SS1 inactive – drive, via terminals)
•
r9720.1 = 0 (SS1 selected)
•
r9722.1 = 0 (SS1 selected)
•
6.
Canceling SS1
No Safety faults and alarms (r0945, r2122, r2132)
•
r9772.22 = r9872.22 = 0 (SS1 deselection via terminal - Control Unit/Motor Module, via
•
PROFIsafe)
r9772.23 = r9872.23 = 0 (SS1 deselection via PROFIsafe - Control Unit/Motor Module, via
•
PROFIsafe)
r9772.0 = r9772.1 = 0 (STO deselected and inactive – CU, via terminals)
•
r9872.0 = r9872.1 = 0 (STO deselected and inactive – MM, via terminals)
•
r9772.2 = r9872.2 = 0 (SS1 inactive – CU and MM, via terminals)
•
r9773.0 = r9773.1 = 0 (STO deselected and inactive – drive, via terminals)
•
r9773.2 = 0 (SS1 inactive – drive, via terminals)
•
r9720.1 = 0 (SS1 selected)
•
r9722.1 = 0 (SS1 selected)
•
r0046.0 = 1 (drive in "switch-on inhibited" state)
7.
•
Acknowledge "switch-on inhibited" and move the drive
8.
Check whether the correct drive is operational
The following is tested:
Correct parameterization of the SS1 function
•
194
Description
Function Manual, (FHS), 11/2009, 6SL3097-4AR00-0BP0
Status
Safety Integrated