F-Di/F-Do Configuration - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

7.3.5

F-DI/F-DO configuration

Inputs screen F-DI
Figure 7-9
NC/NO contact (p10040)
Terminal property F-DI 0-9 (p10040.0 = F-DI 0, ... p10040.9 = F-DI 9), only the property of
the second (lower) digital input is set. Always connect an NC contact to digital input 1
(upper). Digital input 2 can be configured as NO contact.
Activate test mode (p10041)
A check mark at an F-DI defines whether the pair of digital inputs is to be integrated in the
forced dormant error detection test of the assigned power supply (L1+ or L2+) (for additional
information, see chapter "Forced dormant error detection", under Extended Functions).
Safety Integrated
Function Manual, (FHS), 11/2009, 6SL3097-4AR00-0BP0
7.3 Commissioning TM54F by means of STARTER/SCOUT
Inputs screen
Commissioning
139