7.2.1
Prerequisites for commissioning the Safety Integrated function
Prerequisites for commissioning the safety functions (Basic Functions)
1. Commissioning of the drives must be complete.
2. Non-safe pulse suppression must be present, e.g. via
3. The terminals for "Safe Torque Off" must be wired.
4. For operation with SBC, the following applies:
Safety Integrated
Function Manual, (FHS), 11/2009, 6SL3097-4AR00-0BP0
OFF1 = "0" or OFF2 = "0".
If the motor holding brake is connected and parameterized, the holding brake is applied.
A motor with a motor holding brake must be connected to the appropriate terminal of the
module.
7.2 Commissioning Safety Integrated functions
Commissioning
123