Acceptance tests and acceptance reports
9.3 Acceptance tests
No.
r9773.0 = r9773.1 = 1 (STO selected and active – drive, via terminals)
4.
When terminals are grouped for "Safe Torque Off":
5.
r9774.0 = r9774.1 = 1 (STO selected and active - group)
Deselect STO
Check the following:
No Safety faults and alarms (r0945, r2122, r2132)
r9772.17 = r9872.17 = 0 (STO deselection via terminal - Control Unit/Motor Module, via
terminals)
r9772.20 = r9872.20 = 0 (STO deselection via PROFIsafe - Control Unit/Motor Module,
via PROFIsafe)
r9772.0 = r9772.1 = 0 (STO deselected and inactive – Control Unit, via terminals)
r9872.0 = r9872.1 = 0 (STO deselected and inactive – Motor Module, via terminals)
r9773.0 = r9773.1 = 0 (STO deselected and inactive – drive, via terminals)
r9720.0 = 0 (STO selected)
r9722.0 = 0 (STO selected)
When terminals are grouped for "Safe Torque Off":
r9774.0 = r9774.1 = 0 (STO deselected and inactive - group)
r0046.0 = 1 (drive in "switch-on inhibited" state)
Acknowledge "switch-on inhibited" and move the drive
Check that the correct drive is operational.
In so doing, the following is tested:
Correct DRIVE-CLiQ wiring between Control Unit and Motor Modules
Correct assignment of drive No. – Motor Module – motor
The hardware is functioning properly
The switch-off signal paths are wired correctly
Correct assignment of the terminals for STO on the Control Unit
6.
Correct STO grouping (if available)
7.
Correct parameterization of the STO function
8.
Routine for forced dormant error detection of the switch-off signal paths (only via terminal)
9.
198