Extended Functions; Acceptance Tests For Extended Functions - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Acceptance tests and acceptance reports
9.3 Acceptance tests
No.
7.
Check the following:
Brake as in sequence control (p1215 = 1)
Mechanical brake is closed
No Safety faults and alarms (r0945, r2122)
r9772.4 = r9872.4 = 0 (SBC deselection via terminal - Control Unit/Motor Module, via
PROFIsafe)
r9772.0 = r9772.1 = 0 (STO deselected and inactive – CU, via terminals)
r9872.0 = r9872.1 = 0 (STO deselected and inactive – MM, via terminals)
r9773.0 = r9773.1 = 0 (STO deselected and inactive – drive, via terminals)
r0046.0 = 1 (drive in "switch-on inhibited" state)
8.
9.
Acknowledge "Switch-on inhibited" and run the drive
(vertical axis: mechanical brake is released)
Check whether the correct drive is operational.
In so doing, the following is tested:
The brake is connected properly
The hardware is functioning properly
The SBC is parameterized correctly
Routine for the forced dormant error detection of the brake control
9.3.2

Extended Functions

9.3.2.1

Acceptance tests for Extended Functions

If Safety Integrated functions are being used (these take the form of both Basic Functions
and Extended Functions), acceptance tests need to be carried out for any Basic Functions
as well as for Extended Functions.
196
Description
Function Manual, (FHS), 11/2009, 6SL3097-4AR00-0BP0
Status
Safety Integrated

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents