Acceptance tests and acceptance reports
9.3 Acceptance tests
No.
7.
Check the following:
Brake as in sequence control (p1215 = 1)
Mechanical brake is closed
No Safety faults and alarms (r0945, r2122)
r9772.4 = r9872.4 = 0 (SBC deselection via terminal - Control Unit/Motor Module, via
PROFIsafe)
r9772.0 = r9772.1 = 0 (STO deselected and inactive – CU, via terminals)
r9872.0 = r9872.1 = 0 (STO deselected and inactive – MM, via terminals)
r9773.0 = r9773.1 = 0 (STO deselected and inactive – drive, via terminals)
r0046.0 = 1 (drive in "switch-on inhibited" state)
8.
9.
Acknowledge "Switch-on inhibited" and run the drive
(vertical axis: mechanical brake is released)
Check whether the correct drive is operational.
In so doing, the following is tested:
The brake is connected properly
The hardware is functioning properly
The SBC is parameterized correctly
Routine for the forced dormant error detection of the brake control
202
Description
Function Manual, (FHS), 11/2009, 6SL3097-4AR00-0BP0
Status