VLT® Refrigeration Drive FC 103
Operating Guide
Look for any obstructions in the airflow path.
Measure top and bottom clearance of the drive to verify that there is at least 225 mm (9 in) of clearance for adequate airflow.
Ambient conditions
Check that requirements for ambient conditions are met. See the Ambient Conditions section.
Interior of drive
Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion.
Verify that all installation tools have been removed from unit interior.
For enclosures with an IP20/Chassis protection rating, ensure that the unit is mounted to an unpainted metal surface.
Vibration
Ensure that the unit is mounted solidly, or that shock mounts are used, if necessary.
Check for an unusual amount of vibration.
Danfoss A/S © 2020.09
Pre-start Check List
AQ357954340588en-000201 / 130R0881 | 97