Recommended Fuse Ratings For Ul Installation - Danfoss VLT FC 103 Operating

110-800 kw, d9h-d10h and e5h-e6h enclosed drives
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

VLT® Refrigeration Drive FC 103
Operating Guide
Model
Fuse P/N
N560
Mersen NH4GG69V800
N630
Mersen NH4GG69V800
N710
ABB OFAA4AM1000
N800
ABB OFAA4AM1000

5.9.3 Recommended Fuse Ratings for UL Installation

The fuses and MCCBs contained in the enclosed drive are suitable for both short circuit and branch circuit protection. Use only these
fuses.
UL Approval is valid for maximum input voltage of 600 V. Per UL508A, the short-circuit current rating (SCCR) is as follows:
Enclosed drives with a fusible disconnect or fusible disconnect and contactor option have 65 kA SCCR at the rated voltage.
Enclosed drives with single switchgear (mains contactor only or non-fusible disconnect only option) have a 5 kA SCCR, but can
reach 65 kA if the recommended Class fuses are used upstream.
Enclosed drives with the MCCB option have a 65 kA interrupting rating for 380–480 V, and a 50 kA interrupting rating for525–
690 V.
The table values are calculated using correction factors for a 40 °C (104 °F) ambient operating condition and using cables with a
minimum insulation rating of 90 °C (194 °F).
Table 67: Recommended Fuse Ratings for UL Installation, 380–480 V
Model
Fuse P/N (Mersen)
N110
A4J300
N132
A4J350
N160
A4J400
N200
A4J500
N250
A4J600
N315
AABY750
N355
A4BY800
N400
A4BY1000
N450
A4BY1000
N500
A4BY1100
N560
A4BY1200
Table 68: Recommended Fuse Ratings for UL Installation, 525–600 V
Model
Fuse P/N (Mersen)
N110
A4J175
N132
A4J200
N160
A4J250
Danfoss A/S © 2020.09
Fuse size
Rated cur-
rent [A]
4
800
4
800
4
1000
4
1000
Fuse P/N (Danfoss)
Maximum current
[A]
70CPE10965
300
70CPE10966
350
70CPE10522
400
70CPE10968
500
70CPE10523
600
70CPE10969
750
70CPE10974
800
70CPE10975
1000
70CPE10975
1000
70CPE10976
1100
70CPE10977
1200
Fuse P/N (Danfoss)
Maximum current
[A]
70CPE10971
175
70CPE10521
200
70CPE10972
250
Minimum pro-
Maximum fuse
spective SC cur-
rating F1 [A]
rent of the grid
[kA]
19
800
19
800
25
1000
25
1000
Maximum fuse rat-
ing F1 [A]
300
350
400
500
600
750
800
1000
1000
1100
1200
Maximum fuse rat-
ing F1 [A]
175
200
250
AQ357954340588en-000201 / 130R0881 | 91
Electrical Installation
Minimum volt-
Type F1
age rating [V]
690
gG/gL
690
gG/gL
690
aM
690
aM
Minimum voltage
Class F1
rating [V]
500
Class J
500
Class J
500
Class J
500
Class J
500
Class J
500
Class L
500
Class L
500
Class L
500
Class L
500
Class L
500
Class L
Minimum voltage
Class F1
rating [V]
600
Class J
600
Class J
600
Class J

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents