VLT® Refrigeration Drive FC 103
Operating Guide
6.
When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg (grounded
delta), ensure that parameter 14-50 RFI Filter is set to [0] Off to avoid damage to the DC link and to reduce ground capacity
currents.
7.
Tighten the terminals in accordance with the specifications shown in
Example
1
2
Illustration 48: Connection Points for Mains to Input Power Option (Enclosed Drive Configured Without Power Options Cabinet)
1
Lower cover
2
Input power terminals (contactor option is shown)
Danfoss A/S © 2020.09
10.11 Fastener Torque
3
DC terminals
4
Grounding bar
AQ357954340588en-000201 / 130R0881 | 83
Electrical Installation
Ratings.
3
4
Need help?
Do you have a question about the VLT FC 103 and is the answer not in the manual?
Questions and answers