Non-Fusible Disconnect Switches - Danfoss VLT FC 103 Operating

110-800 kw, d9h-d10h and e5h-e6h enclosed drives
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

VLT® Refrigeration Drive FC 103
Operating Guide
Table 116: Fusible Disconnect Switches for N400–N630 Models, 525–690 V
N400
630 A/690 V
IEC
ABB P/N
OS630D30P
UL
600 A/600 V
ABB P/N
OS600J30
Table 117: Fusible Disconnect Switches for N710–N800 Models, 525–690 V
IEC
ABB P/N
UL
ABB P/N

10.8.4 Non-fusible Disconnect Switches

The non-fusible disconnector switch is an option. All units ordered and supplied with a factory-installed, non-fusible disconnect
switch require a UL Class fuse to meet 65kA SCCR for the drive system.
Table 118: Non-fusible Disconnect Switches for N110–N315 Models, 380–480 V
N110
400 A/600 V
IEC
ABB P/N
OT400E30
UL
400 A/690 V
ABB P/N
OT400U30
Table 119: Non-fusible Disconnect Switches for N355–N560 Models, 380–480 V
N355
1000 A/600 V
IEC
ABB P/N
OT1000E30
UL
800 A/690 V
ABB P/N
OT800U30
Table 120: Non-fusible Disconnect Switches for N110–N315 Models, 525–690 V
N110
IEC
400 A/600 V
ABB P/N
OT400E30
400 A/690 V
UL
ABB P/N
OT400U30
Danfoss A/S © 2020.09
N450
N500
630 A/690 V
1250 A/690 V
OS630D30P
OS1250D30P
600 A/600 V
800 A/600 V
OS600J30
OS800L30
N710
1250 A/690 V
OS1250D30P
1200 A/600 V
OS1200L30
N132
N160
400 A/600 V
400 A/600 V
OT400E30
OT400E30
400 A/690 V
400 A/690 V
OT400U30
OT400U30
N400
1000 A/600 V
OT1000E30
1200 A/690 V
OT1200U30
N132
N160
400 A/600 V
400 A/600 V
OT400E30
OT400E30
400 A/690 V
400 A/690 V
OT400U30
OT400U30
N560
1250 A/690 V
OS1250D30P
800 A/600 V
OS800L30
N800
1250 A/690 V
OS1250D30P
1200 A/600 V
OS1200L30
N200
630 A/600 V
OT630E30
600 A/690 V
OT600U30
N450
N500
1250 A/600 V
1250 A/600 V
OT1250E30
OT1250E30
1200 A/690 V
1200 A/690 V
OT1200U30
OT1200U30
N200
630 A/600 V
OT630E30
600 A/690 V
OT600U30
AQ357954340588en-000201 / 130R0881 | 159
Specifications
N630
1250 A/690 V
OS1250D30P
800 A/600 V
OS800L30
N250
N315
630 A/600 V
630 A/600 V
OT630E30
OT630E30
600 A/690 V
800 A/690 V
OT600U30
OT800U30
N560
1250 A/600 V
OT1250E30
1200 A/690 V
OT1200U30
N250
N315
630 A/600 V
630 A/600 V
OT630E30
OT630E30
600 A/690 V
600 A/690 V
OT600U30
OT600U30

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC 103 and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF