VLT® Refrigeration Drive FC 103
Operating Guide
9.3.2 WARNING 1, 10 Volts Low
Cause
The control card voltage is less than 10 V from terminal 50. Remove some of the load from terminal 50, as the 10 V supply is overloa-
ded. Maximum 15 mA or minimum 590 Ω.
A short circuit in a connected potentiometer or incorrect wiring of the potentiometer can cause this condition.
Troubleshooting
•
Remove the wiring from terminal 50. If the warning clears, the problem is with the wiring. If the warning does not clear, replace
the control card.
9.3.3 WARNING/ALARM 2, Live Zero Error
Cause
This warning or alarm only appears if programmed in parameter 6-01 Live Zero Timeout Function. The signal on 1 of the analog inputs
is less than 50% of the minimum value programmed for that input. Broken wiring or a faulty device sending the signal can cause this
condition.
Troubleshooting
•
Check connections on all analog mains terminals.
-
Control card terminals 53 and 54 for signals, terminal 55 common.
-
VLT® General Purpose I/O MCB 101 terminals 11 and 12 for signals, terminal 10 common.
-
VLT® Analog I/O Option MCB 109 terminals 1, 3, and 5 for signals, terminals 2, 4, and 6 common.
•
Check that the drive programming and switch settings match the analog signal type.
•
Perform an input terminal signal test.
9.3.4 WARNING/ALARM 3, No Motor
Cause
No motor is connected to the output of the drive.
9.3.5 WARNING/ALARM 4, Mains Phase Loss
Cause
A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input
rectifier. Options are programmed in parameter 14-12 Function at Mains Imbalance.
Troubleshooting
•
Check the supply voltage and supply currents to the drive.
9.3.6 WARNING 5, DC Link Voltage High
Cause
The DC-link voltage (DC) is higher than the high-voltage warning limit. The limit depends on the drive voltage rating. The unit is still
active.
9.3.7 WARNING 6, DC Link Voltage Low
Cause
The DC-link voltage (DC) is lower than the low voltage warning limit. The limit depends on the drive voltage rating. The unit is still
active.
9.3.8 WARNING/ALARM 7, DC Overvoltage
Cause
If the DC-link voltage exceeds the limit, the drive trips after a certain time.
Troubleshooting
•
Extend the ramp time.
•
Change the ramp type.
•
Activate the functions in parameter 2-10 Brake Function.
•
Increase parameter 14-26 Trip Delay at Inverter Fault.
•
If the alarm/warning occurs during a power sag, use kinetic back-up (parameter 14-10 Mains Failure).
•
Connect a brake resistor.
Danfoss A/S © 2020.09
Maintenance, Diagnostics, and
Troubleshooting
AQ357954340588en-000201 / 130R0881 | 123
Need help?
Do you have a question about the VLT FC 103 and is the answer not in the manual?
Questions and answers