Fail-Safe signal module (SM) I/O configuration

5.2 Configuring common F-parameters

5.2
Configuring common F-parameters
Table 5- 1
Common F-parameters
F-parameters
Manual assignment of
F-monitoring time
F-monitoring time
1
F-source address
F-destination address
Behavior after channel
fault
Reintegration after
channel fault
(not available for the SM
1226 F-DQ 2 x Relay)
You set the "Default F-monitoring time for central F-IO" in the F-parameters of the fail-safe CPU. STEP 7 uses this
1
number to set the F-monitoring time in each fail-safe SM unless you select the check box for "Manual Assignment of F-
monitoring time" in that module configuration and assign a different time.
Refer to the SIMATIC, Industrial Software, SIMATIC Safety - Configuring and Programming,
Programming and Operating Manual
(http://support.automation.siemens.com/WW/view/en/54110126/0/en) for further F-parameter
information
106
Description
You must select the check box to change
F-monitoring time from the central value propa-
gated by the fail-safe CPU.
Watchdog timer monitoring safety-related
communication between the fail-safe CPU and
fail-safe SM (PROFIsafe monitoring time)
Unique network-wide address for the fail-safe
CPU
CPU-wide unique address (usually in descend-
ing order, starting with 65534).
Response by the fail-safe SM to channel faults
such as a short-circuit, overload, or discrepancy
error.
You have two methods, manual and automatic,
to reintegrate your fail-safe SM channels after a
channel fault. You can choose to reintegrate in
one of three ways:
All channels automatically (no acknowl-
edgement necessary for reintegration)
All channels manually (acknowledgement
necessary for reintegration)
Adjustable (channel-by-channel; some
channels automatically reintegrated and
some channels manually reintegrated)
.
Default
Options
Check box
Check box:
deselected
150 ms
1 to 65535 ms
1
You can configure the
F-source address
using the fail-safe
CPU parameter "Basis
for PROFIsafe ad-
dresses".
-
1 to 65534
Passivate channel
Not configurable in the
fail-safe SM
Adjustable
S7-1200 Functional Safety Manual
Manual, 02/2015, A5E03470344-AA
Selected
Deselected
Adjustable
All channels
automatically
All channels
manually