Example On How To Connect A Wye Connected Three-Phase Ct Set To The Ied - ABB Relion 670 Series Applications Manual

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 4
Analog inputs
4.2.2.5

Example on how to connect a wye connected three-phase CT set to the IED

Figure
12
gives an overview of the actions which are needed to make this measurement available to the
built-in protection and control functions within the IED as well.
A
CT 600/5
Star Connected
Protected Object
ANSI13000002 V4 EN-US
Figure 12:
Wye connected three-phase CT set with wye point towards the protected object
56
It is recommended to:
use 1A rated CT input into the IED in order to connect CTs with 1A and 2A
secondary rating
use 5A rated CT input into the IED in order to connect CTs with 5A and 10A
secondary rating
gives an example about the wiring of a wye connected two-phase CT set to the IED. It
For correct terminal designations, see the connection diagrams valid for the
delivered IED.
B
C
I_A
I_B
I_C
I_N
© Copyright 2017 Hitachi Power Grids. All rights reserved
IED
1
2
3
1MRK 511 407-UUS Rev. J
4
SMAI2
BLOCK
AI3P
REVROT
AI1
5
^GRP2_A
AI2
^GRP2_B
AI3
^GRP2_C
AI4
^GRP2_N
AIN
ANSI13000002-4-en.vsdx
Phasor measurement unit RES670
Application manual
SEMOD55055-352 v11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion res670 a20Relion res670 b20

Table of Contents