ABB Relion 670 Series Applications Manual page 197

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 407-UUS Rev. J
5.
Set base voltage value to the rated generator phase-to-phase voltage in kV
6.
Enable one overcurrent step (for example, OC1)
7.
Select
8.
If required set minimum operating time for this curve by using parameter
value 0.05s)
9.
Set
10. Set
11. Set
12. Set
13. Set
14. Set
Proper operation of the CVGAPC function made in this way can easily be verified by secondary
injection. All other settings can be left at the default values. Furthermore the other built-in
protection elements can be used for other protection and alarming purposes.
11.1.3.6
Loss of excitation protection for a generator
Example will be given how by using positive sequence directional overcurrent protection element
within a CVGAPC function, loss of excitation protection for a generator can be achieved. Let us
assume that from rated generator data the following values are calculated:
Maximum generator capability to contentiously absorb reactive power at zero active loading
38% of the generator MVA rating
Generator pull-out angle 84 degrees
This functionality can be achieved by using one CVGAPC function. The following shall be done in
order to insure proper operation of the function:
1.
Connect three-phase generator currents and three-phase generator voltages to one CVGAPC
instance (for example, GF02)
2.
Set parameter
3.
Set parameter
4.
Set base current value to the rated generator current primary amperes
5.
Set base voltage value to the rated generator phase-to-phase voltage in kV
6.
Set parameter
7.
Set parameter
8.
Set parameter
9.
Enable one overcurrent step (for example, OC1)
10. Select parameter
11. Set parameter
12. Set parameter
13. Set parameter
14. Set parameter
15. Set parameter
Proper operation of the CVGAPC function made in this way can easily be verified by secondary
injection. All other settings can be left at the default values. However it shall be noted that set
values for RCA & ROA angles will be applicable for OC2 step if directional feature is enabled for this
step as well. Figure
Furthermore the other build-in protection elements can be used for other protection and alarming
purposes.
Phasor measurement unit RES670
Application manual
CurveType_OC1 to value ANSI Very inv
PickupCurr_OC1 to value 185%
VCntrlMode_OC1 to On
VDepMode_OC1 to Slope
VDepFact_OC1 to value 0.25
VHighLimit_OC1 to value 100%
VLowLimit_OC1 to value 25%
CurrentInput to PosSeq
VoltageInput to PosSeq
RCADir to value -84 degree (that is, current lead voltage for this angle)
ROADir to value 90 degree
LowVolt_VM to value 5%
CurveType_OC1 to value IEC Def. Time
PickupCurr_OC1 to value 38%
tDef_OC1 to value 2.0s (typical setting)
DirMode_OC1 to Forward
DirPrinc_OC1 to IcosPhi&V
ActLowVolt1_VM to Block
77
shows overall protection characteristic
© Copyright 2017 Hitachi Power Grids. All rights reserved
Section 11
Multipurpose protection
tMin_OC1 (default
M13088-182 v3
191