ABB Relion 670 Series Applications Manual page 328

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 22
Basic IED functions
22.5.1
Identification
Function description
Primary system values
22.5.2
Application
The rated system frequency and phase rotation direction are set under Main menu/
Configuration/ Power system/ Primary Values in the local HMI and PCM600 parameter setting
tree.
22.5.3
Setting guidelines
Set the system rated frequency. Refer to section
description on frequency tracking.
22.6
Summation block 3 phase 3PHSUM
22.6.1
Application
The analog summation block 3PHSUM function block is used in order to get the sum of two sets of
3 phase analog signals (of the same type) for those IED functions that might need it.
22.6.2
Setting guidelines
The summation block receives the three-phase signals from SMAI blocks. The summation block
has several settings.
SummationType : Summation type ( Group 1 + Group 2 , Group 1 - Group 2 , Group 2 - Group 1 or –
(Group 1 + Group 2) ).
DFTReference : The reference DFT block ( InternalDFT Ref , DFTRefGrp1 or External DFT ref ) .
DFTRefGrp1 : This setting means use own internal adaptive DFT reference ( this setting makes the
SUM3PH self DFT adaptive, that is, it will use the measured frequency for the summation signal to
adapt DFT).
InternalDFTRef : Gives fixed window DFT (to nominal system frequency).
ExternalDFTRef : This setting means that the DFT samples-per-cycle (adaptive DFT) will be
controlled by SMAI1 SPFCOUT.
FreqMeasMinVal : The minimum value of the voltage for which the frequency is calculated,
expressed as percent of
GlobalBaseSel : Selects the global base value group used by the function to define ( IBase ), ( VBase )
SBase ).
and (
322
IEC 61850
identification
PRIMVAL
VBase base voltage setting (for each instance x).
© Copyright 2017 Hitachi Power Grids. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
"Signal matrix for analog inputs SMAI"
Phasor measurement unit RES670
1MRK 511 407-UUS Rev. J
GUID-B8B3535D-227B-4151-9E98-BEB85F4D54DE v1
M15288-3 v6
M15292-3 v2
for
SEMOD55968-1 v2
SEMOD56004-4 v3
SEMOD56006-4 v7