Section 22
Basic IED functions
For task time group 2 this gives the following settings:
SMAI1:13 – SMAI12:24:
(SMAI6:42)
For task time group 3 this gives the following settings:
SMAI1:25 – SMAI12:36:
(SMAI6:42)
For task time group 4 this gives the following settings:
SMAI1:37:
DFTReference = DFTRefGrp6 for SMAI1:37 to use SMAI6:42 as reference (see Figure 124) SMAI2:38 –
SMAI12:48:
22.12
Test mode functionality TESTMODE
22.12.1
Application
The protection and control IEDs may have a complex configuration with many included functions.
To make the testing procedure easier, the IEDs include the feature that allows individual blocking
of a single-, several-, or all functions.
This means that it is possible to see when a function is activated or trips. It also enables the user
to follow the operation of several related functions to check correct functionality and to check
parts of the configuration, and to check parts.
22.12.1.1
IEC 61850 protocol test mode
The function block TESTMODE has implemented the extended testing mode capabilities for IEC
61850 Ed2 systems. Operator commands sent to the function block TESTMODE determine the
behavior of the functions. The command can be given remotely from an IEC 61850 client or from
the LHMI under the Main menu/Test/Function test modes/Communication/Station
Communication/IEC61850 LD0 LLN0/LD0LLN0:1. The possible values of the function block
TESTMODE are described in
There is no setting in PCM600 via PST for the TESTMODE function block.
The DataObject Mod of the Root LD.LNN0 can be set on the LHMI under Main menu/Test/
Function test modes/Communication/Station communication/IEC61850 LD0 LLN0/LD0LLN0:1
On , Off , TestBlocked , Test or Blocked .
to
332
DFTReference = ExternalDFTRef to use DFTSPFC input as reference
DFTReference = ExternalDFTRef to use DFTSPFC input as reference
DFTRefExtOut = DFTRefGrp6 to route SMAI6:42 reference to the SPFCOUT output,
DFTReference = DFTRefGrp6 to use SMAI6:42 as reference.
Communication protocol manual, IEC 61850 Edition 1 and Edition 2 .
To be able to set the function block TESTMODE remotely, the setting via path on
LHMI and in PST: Main menu/Configuration/Communication/ Station
Communication/IEC61850-8-1/IEC61850-8-1:1
Off . The possible values of the parameter RemoteModControl are Off ,
to
Maintenance or All levels . The Off value denies all access to function block
TESTMODE from remote,
(orCat) is
Maintenance and All levels allow any orCat.
© Copyright 2017 Hitachi Power Grids. All rights reserved
RemoteModControl may not be set
Maintenance requires that the category of the originator
1MRK 511 407-UUS Rev. J
M11407-3 v9
GUID-82998715-6F23-4CAF-92E4-05E1A863CF33 v5
Phasor measurement unit RES670