1MRK 511 407-UUS Rev. J
The inverse time delay is defined as:
TDSN (3I 3V cos (reference))
=
t
inv
EQUATION2069 V1 EN-US
The function can be set
GlobalBaseSel : It is used to select a GBASVAL function for reference of base values.
RotResU : It is a setting for rotating the polarizing quantity (3V
parameter is set to 180 degrees by default in order to inverse the residual voltage (3V
calculate the reference voltage (-3V
quantity for directionality, it is important to set this parameter correctly.
With the setting
OpModeSel set to 3I0cosfi the current component in the direction equal to the characteristic
With
RCADir has the maximum sensitivity. The characteristic for RCADir is equal to 0° is shown in
angle
Figure 66.
ANSI06000648 V1 EN-US
Figure 66: Characteristic for RCADir equal to 0°
The characteristic is for
Phasor measurement unit RES670
Application manual
f
×
×
×
0
0
f
×
3I 3V cos (measured)
0
0
Enabled/Disabled with the setting of Operation .
OpModeSel the principle of directional function is chosen.
V
RCA = 0°, ROA = 90°
ref
3I
= ang(3I
3I
RCADir equal to -90° is shown in Figure 67.
© Copyright 2017 Hitachi Power Grids. All rights reserved
-jRCADir
e
). Since the reference voltage is used as the polarizing
0
0
) - ang(3V
)
0
ref
-3V
=V
0
ref
cos
0
en06000648_ansi.vsd
Current protection
) by 0 or 180 degrees. This
0
0
Section 8
(Equation 55)
) to
145