Section 6
Wide area measurement system
predefined inputs for Frequency Trigger, Rate of Change of Frequency trigger, Magnitude High
and Magnitude Low triggers.
IEC140000118 V2 EN-US
Figure 32: Multiple instances of PMUREPORT function block
Figure
33
visible in the bottom of each function block. For each instance, there are four separate
PHASORREPORT blocks including 32 configurable phasor channels (8 phasor channels in each
PHASORREPORT block). Each phasor channel can be configured as a 3-phase (symmetrical
components positive/negative/zero) or single-phase phasor (A/B/C).
IEC140000119 V2 EN-US
Figure 33: Multiple instances of PHASORREPORT blocks
Figure
34
visible in the bottom of each function block. For each instance, there are three separate
ANALOGREPORT blocks capable of reporting up to 24 Analog signals (8 Analog signals in each
ANALOGREPORT block). These can include for example transfer of active and reactive power or
reporting the milliampere input signals to the PDC clients as defined in IEEE IEC/IEEE 60255-118
(C37.118) data frame format.
86
shows both instances of the PHASORREPORT function blocks. The instance number is
shows both instances of ANALOGREPORT function blocks. The instance number is
© Copyright 2017 Hitachi Power Grids. All rights reserved
IEC140000118-2-en.vsd
IEC140000119-2-en.vsd
Phasor measurement unit RES670
1MRK 511 407-UUS Rev. J
Application manual