ABB Relion 670 Series Applications Manual page 303

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 407-UUS Rev. J
19.4.2.3
Setting guidelines
Settings
The parameters for the multiple command function are set via PCM600.
Mode setting sets the outputs to either a Steady or Pulsed mode.
The
19.5
SPA communication protocol
19.5.1
Application
SPA communication protocol is an alternative to IEC 60870-5-103, and they use the same rear
communication port.
When communicating with a PC connected to the utility substation LAN via WAN and the utility
office LAN (see Figure 113), and when using the rear optical Ethernet port, the only hardware
required for a station monitoring system is:
Optical fibers from the IED to the utility substation LAN
PC connected to the utility office LAN
Remote
monitoring
ANSI05000715 V4 EN-US
Figure 113: SPA communication structure for a remote monitoring system via a substation
SPA communication is mainly used for the Station Monitoring System. It can include different IEDs
with remote communication possibilities. Connection to a PC can be made directly (if the PC is
located in the substation), via a telephone modem through a telephone network with ITU (former
CCITT) characteristics or via a LAN/WAN connection.
glass
plastic
Functionality
The SPA protocol V2.5 is an ASCII-based protocol for serial communication. The communication is
based on a master-slave principle, where the IED is a slave and the PC is the master. Only one
Phasor measurement unit RES670
Application manual
Utility LAN
LAN, WAN and utility LAN
<1000 m according to optical budget
<25 m (inside cubicle) according to optical budget
© Copyright 2017 Hitachi Power Grids. All rights reserved
WAN
IED
IED
Station communication
Substation LAN
IED
ANSI05000715-4-en.vsd
Section 19
SEMOD119915-1 v1
M14789-4 v3
IP14614-1 v1
IP14785-1 v1
SEMOD115767-5 v7
SEMOD115767-25 v3