Section 6
Wide area measurement system
3.
ANALOGREPORT is the function block responsible for reporting the analog values. Each
instance of ANALOGREPORT function block has 24 analog channels with the following setting
parameters; where X is a number from 1 to 24:
100
PhasorXReport : Enables/Disables the phasor channel X (reporting of PhasorX) by
On / Off setting.
choosing
PhasorX : The group selector for PhasorX. Here, the user can select the type of reported
synchrophasor from the phasor channel X as either a 3-phase symmetrical component
or a single-phase phasor. The options are as follows:
A
B
C
NEGSEQ
POSSEQ
ZEROSEQ
PhasorXUseFreqSrc : Enables/Disables the contribution of Phasor channel X in
automatic frequency source selection by choosing
connected preprocessor block delivers the frequency data, derived from the analog
input AC voltage values, to the respective voltage phasor channel. Every phasor channel
has a user-settable parameter (
data for reporting to the PDC client. It is very important to set this parameter to
the voltage-connected phasor channels. There is an automatic frequency source
selection logic to ensure an uninterrupted reporting of the system frequency to the PDC
client. More information is available under the section
AnalogXRange : This parameter defines a range between -AnalogXRange and
+AnalogXRange for AnalogX value. The range will be used by the IED to apply a proper
scale factor to the AnalogX values when
ANUNIT field of the configuration frames 1, 2 organization and the 8-byte ANSCALE field
of the configuration frame 3 organization defined in 60255-118-2011 message format.
AnalogXRange value can be a number between 3277.0 and 10000000000 . This
The
setting is only important if the AnalogDataType setting is selected as
information is available under the section
AnalogXUnitType : Unit type for analog signal X. It refers to the 4-byte ANUNIT field of
the configuration frames 1, 2 organization defined in 60255-118-2011 message format.
The options are
Single point-on-wave , RMS of analog input and Peak of analog input .
© Copyright 2017 Hitachi Power Grids. All rights reserved
On / Off setting. Each voltage-
PhasorXUseFreqSrc ) to be used as a source of frequency
Frequency
Integer format is used. It refers to the 4-byte
Scaling Factors for ANALOGREPORT
1MRK 511 407-UUS Rev. J
On for
reporting.
Integer . More
channels.
Phasor measurement unit RES670
Application manual