ABB Relion 670 Series Applications Manual page 169

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 407-UUS Rev. J
Section 9
9.1
Two step undervoltage protection UV2PTUV (27)
9.1.1
Identification
Function description
Two step undervoltage protection
9.1.2
Application
Two-step undervoltage protection function (UV2PTUV ,27) is applied to power system elements,
such as generators, transformers, motors and power lines in order to detect low voltage
conditions. It is used as a supervision and fault detection function for other protection functions
as well, to increase the security of a complete protection system. Low voltage conditions are
caused by abnormal operation or faults in the power system, such as:
Malfunctioning of a voltage regulator or wrong settings under manual control (symmetrical
voltage decrease)
Overload (symmetrical voltage decrease)
Short circuits, often as phase-to-ground faults (unsymmetrical voltage decrease)
UV2PTUV (27) is used in combination with overcurrent protections, either as restraint or in logic
"and gates" of the trip signals issued by the two functions. It can also be used to:
Detect no voltage conditions, for example, before the energization of a HV line or for
automatic breaker trip in case of a blackout
Initiate voltage correction measures, like insertion of shunt capacitor banks to compensate
for reactive load and thereby increasing the voltage
Disconnect apparatuses, like electric motors, which will be damaged when subject to service
under low voltage conditions.
The function has a high measuring accuracy and a settable hysteresis to allow applications to
control reactive load.
In many cases, UV2PTUV (27) is a useful function in circuits for local or remote automation
processes in the power system.
9.1.3
Setting guidelines
All the voltage conditions in the system where UV2PTUV (27) performs its functions should be
considered. The same also applies to the associated equipment, its voltage and time
characteristic.
Phasor measurement unit RES670
Application manual
Voltage protection
IEC 61850
identification
UV2PTUV
© Copyright 2017 Hitachi Power Grids. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
27
3U<
V2 EN-US
SYMBOL-R-2U-GREATER-THAN
Section 9
Voltage protection
IP14544-1 v3
M16876-1 v7
M13790-3 v8
M13851-3 v9
163

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion res670 a20Relion res670 b20

Table of Contents