Section 19
Station communication
Using PTP for synchronizing the MU
SAM600 VT
IEC17000040 V1 EN-US
Figure 109: Setting example with PTP synchronization
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/
TIMESYNCHGEN:1/IEC61850-9-2:
HwSyncSrc : is not used as the SW-time and HW-time are connected with each other due to
PTP
SyncLostMode : set to Block to block protection functions if time synchronization is lost or set
BlockOnLostUTC if the protection functions are to be blocked when global common
to
synchronization is lost
SyncAccLevel : can be set to 1μs since this corresponds to a maximum phase angle error of
0.018 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Communication/Ethernet
configuration/Access point/AP_X:
Operation: On
PTP: On
Two status monitoring signals can be:
292
IED
9-2
PTP
SAM600 TS
© Copyright 2017 Hitachi Power Grids. All rights reserved
SAM600 CT
IEC17000040-1-en.vsdx
1MRK 511 407-UUS Rev. J
Phasor measurement unit RES670
Application manual