Description of configuration B20

The configuration of the IED is shown in
RES670 B20 configuration is applicable for a typical double busbar single breaker arrangement
monitoring up to six bays. RES670 B20 is delivered in ¾, and full (1/1)19" rack casing. For this
application 24 analog inputs are used, thus two transformer modules (TRM) with 12 analog inputs
(9I+3U) per TRM are available in B20 standard configuration. As shown in
configuration as a PMU is measuring two 3-phase voltages of the busbars and six 3-phase currents
of bays 1 to 6. There are two instances of PMU reporting functionality available in B20
configuration, meaning two independent IEEE C37.118/1344 data streams. Each instance of PMU is
reporting frequency-deviation and rate-of-change-of-frequency data. In the standard B20
configuration, in addition to frequency data, first instance of PMU (first data stream) is reporting
32 synchrophasors over IEEE C37.118/1344; that is eight 3-phase synchrophasors and 24 single
phase synchrophasors corresponding to the AC voltage and current measurements. Second
instance of PMU (second data stream) is reporting 16 synchrophasors over IEEE C37.118/1344; that
is four 3-phase synchrophasors and 12 single phase synchrophasors corresponding to the AC
voltage and current measurements. The number of synchrophasor reporting channels on second
instance of PMU can be extended to 32 channels per request. This can be done when ordering the
RES670 B20 configuration.
In addition, each data stream includes 16 analog and 16 binary reporting channels over IEEE
C37.118/1344 in the standard configuration. The number of analog and binary reporting channels
Phasor measurement unit RES670
Application manual
Other Functions available from the function library
71
DELI SPVC
71
Optional Functions
87
CCS SPVC
51_67 4(3I>)
OC4 PTOC
Block diagram for configuration A20
© Copyright 2017 Hitachi Power Grids. All rights reserved
RES670 A20 – Phasor Measurement Unit, 3 bays, single busbar,
WA1_VT
WA1
DFR/SER DR
DRP RDRE
BAY03_CT
MET
P/Q
MET
I
CV MMXN
C MMXU
BAY02_CT
MET
P/Q
MET
I
CV MMXN
C MMXU
BAY01_CT
MET
P/Q
MET
I
CV MMXN
C MMXU
7
MET W/Varh
3
Control
DELTAI
7V_78V
DELTAU
DELTA
DELV SPVC
DEL SPVC
ETP MMTR
Q CBAY
3
MET
UN
Control
S SIML
S XCBR
VN MMXU
INd/I
ITHD
ITHD
2(I>/U<)
51N_67N
4(IN>)
U>/I<
CHM MHAI
CV GAPC
EF4 PTOC
FUF SPVC
78
Ucos
67N
IN>
VTHD UTHD
68
Zpsb
OOS PPAM
SDE PSDE
VHM MHAI
ZMBU RPSB
figure
4.
12AI (9I+3U)
81
df/dt
SA PFRC
81
f>
SA PTOF
81U
f<
SA PTUF
27
2(3U<)
UV2 PTUV
59
2(3U>)
OV2 PTOV
MET
U
V MMXU
MET
Usqi
V MSQI
IEEE Std 1344
PMU REP
IEEE Std C37.118
MET
Isqi
C MSQI
Phasor
data
IEEE Std 1344
MET
Isqi
C MSQI
PMU REP
IEEE Std C37.118
MET
Isqi
C MSQI
94
1→0
63
SMP PTRC
S SCBR
S SIMG
32
P>
37
P<
46I2
4(I2>)
GOP PDOP
GUP PDUP
NS4 PTOC
IEC140000122-4-en.vsdx
GUID-E8A586F6-E450-4B5E-AF00-1DC9A197A2A6 v6
figure
4, RES670 B20
Section 3
Configuration
45