ABB Relion 670 Series Applications Manual page 116

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 7
Impedance protection
RLdInFw
EQUATION1350 V1 EN-US
kLdRFw
EQUATION1351 V1 EN-US
Also check if this minimum setting satisfies the required speed for detection of consecutive
oscillations. This requirement will be satisfied if the proposed setting of
than 10 ms, see equation 31.
tP
2
max
EQUATION1352 V1 EN-US
The final proposed settings are as follows:
RLdOutFw = 123.5Ω
kLdRFw = 0.61
tP1 = 30 ms
tP2 = 10 ms
Consider RLdInFw = 75.0Ω.
LdAngle
EQUATION1737-ANSI V1 EN-US
Consider equation 33,
LdAngle
PSD
EQUATION1739-ANSI V1 EN-US
110
Z
S
=
d
max1
æ
ö
×
-
2 tan
in
min
ç
÷
è
2
ø
RLdInFw
=
=
max1
RLdOutFw
123.5
d
d
-
° -
91.5
=
=
In
Out
×
°
×
f
360
7 360
sc
Do not forget to adjust the setting of load encroachment resistance
Phase selection with load encroachment (ZMFPDIS) to the value equal to or less
than the calculated value RLdInFw. It is at the same time necessary to adjust the
load angle in ZMFPDIS to follow the condition presented in equation 32.
Index PHS designates correspondence to ZMFPDIS function and index PSD the
correspondence to ZMBURPSB (68) function.
é
tan(
LdAngle
³
arctan
ê
PHS
ë
KLdRFw
=
°
25
j
=
max
© Copyright 2017 Hitachi Power Grids. All rights reserved
155.75
=
=
75.8
æ
ö
91.5
×
2 tan
ç
÷
è
2
ø
75.8
=
0.61
°
64.5
=
10.7
ms
°
ù
)
PSD
ú
û
1MRK 511 407-UUS Rev. J
W
tP2 time remains higher
Phasor measurement unit RES670
(Equation 29)
(Equation 30)
(Equation 31)
RLdFwd in
(Equation 32)
(Equation 33)
Application manual