Section 4
Analog inputs
A
B
CT 800/1
Wye Connected
Protected Object
ANSI11000026 V5 EN-US
Figure 13:
Wye connected three-phase CT set with its wye point away from the protected object
In the example, everything is done in a similar way as in the above described example (Figure 12).
The only difference is the setting of the parameter
TRM (item 2 in Figure
CTprim =600A
CTsec =5A
CTWyePoint =FromObject
The ratio of the first two parameters is only used inside the IED. The third parameter as set in this
example will negate the measured currents in order to ensure that the currents are measured
towards the protected object within the IED.
A third alternative is to have the residual/neutral current from the three-phase CT set connected
to the IED as shown in Figure 13.
58
C
1
IC
IB
IA
13
and 12):
© Copyright 2017 Hitachi Power Grids. All rights reserved
IED
2
3
CTStarPoint of the used current inputs on the
1MRK 511 407-UUS Rev. J
4
SMAI_20_2
BLOCK
AI3P
REVROT
AI1
5
^GRP2_A
AI2
^GRP2_B
AI3
^GRP2_C
AI4
^GRP2N
AIN
ANSI11000026-5-en-.vsd
Phasor measurement unit RES670
Application manual