ABB Relion 670 Series Applications Manual page 310

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 19
Station communication
Disturbance Recordings
For each input of the Disturbance recorder function there is a setting for the information number
of the connected signal. The function type and the information number can be set to any value
between 0 and 255. To get INF and FUN for the recorded binary signals, there are parameters on
the disturbance recorder for each input. The user must set these parameters to whatever he
connects to the corresponding input.
Refer to description of Main Function type set on the local HMI.
Recorded analog channels are sent with ASDU26 and ASDU31. One information element in these
ASDUs is called ACC, and it indicates the actual channel to be processed. The channels on
disturbance recorder are sent with an ACC as shown in Table 32.
Table 32:
DRA#-Input
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
Table continues on next page
304
Channels on disturbance recorder sent with a given ACC
© Copyright 2017 Hitachi Power Grids. All rights reserved
ACC
1
2
3
4
5
6
7
8
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
1MRK 511 407-UUS Rev. J
IEC103 meaning
IA
IB
IC
IG
VA
VB
VC
VG
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Phasor measurement unit RES670
Application manual
M17109-141 v8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion res670 a20Relion res670 b20

Table of Contents