All start and directional outputs are mapped to the logical node data model of the trip function
and provided via the IEC 61850 attributes dirGeneral, dirPhsA, dirPhsB, dirPhsC, and dirNeut.
15.1.3.6
Blocking of the function block
Total block of the trip function is done by activating the input BLOCK and can be used to disable
the outputs of the trip logic in the event of internal failures. Block of lockout output is achieved by
activating the input BLKLKOUT.
15.1.4
Setting guidelines
The parameters for the trip function SMPPTRC (94) are set via the local HMI or PCM600.
Operation : Sets the mode of operation. Disabled switches the tripping off. The normal selection is
Enabled .
Program : Sets the required tripping scheme. Normally 3 phase or 1p/3p is used.
TripLockout : Sets the scheme for lockout. Disabled only activates the circuit breaker close lockout
output.
outputs. The normal selection is
All lockout : Sets the scheme for lockout. Disabled only activates lockout through the output
CLLKOUT.
Disabled .
is
tTripMin : Sets the required minimum duration of the trip pulse. It should be set to ensure that the
circuit breaker is opened correctly. The normal setting is
tWaitForPHS : Sets a duration after any of the inputs 1PTRZ or 1PTRGF has been activated during
which external pole selection must operate in order to get a single pole trip. If no pole selection
has been achieved, a three-pole trip will be issued after this time has elapsed.
tEvolvingFault : Secures two- or three-pole tripping depending on Program selection during
evolving faults.
15.2
Trip matrix logic TMAGAPC
15.2.1
Identification
Function description
Trip matrix logic
Phasor measurement unit RES670
Application manual
Enabled activates the circuit breaker close lockout output and latches the TRIP related
Enabled additionally allows lockout activation via the trip inputs. The normal selection
© Copyright 2017 Hitachi Power Grids. All rights reserved
Disabled .
IEC 61850
IEC 60617
identification
identification
TMAGAPC
-
0.150s .
ANSI/IEEE C37.2
device number
-
Section 15
Logic
M14828-21 v5