ABB Relion 670 Series Applications Manual page 256

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 16
Monitoring
Setting
k
VGenZeroDb
IGenZeroDb
VBase (set in
Global base)
IBase (set in
Global base)
16.2
Gas medium supervision SSIMG (63)
16.2.1
Function revision history
Document
revision
A
B
C
D
E
F
G
H
16.2.2
Identification
Function description
Insulation gas monitoring function
16.2.3
Application
Gas medium supervision (SSIMG ,63) is used for monitoring the circuit breaker condition. Proper
arc extinction by the compressed gas in the circuit breaker is very important. When the pressure
becomes too low compared to the required value, the circuit breaker operation shall be blocked to
minimize the risk of internal failure. Binary information based on the gas pressure in the circuit
breaker is used as an input signal to the function. The function generates alarms based on the
received information.
250
Short description
Low pass filter coefficient for
power measurement, V and I
Zero point clamping in % of
Vbase
Zero point clamping in % of
Ibase
Base setting for voltage level
in kV
Base setting for current level
in A
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
Binary quality inputs SENPRESQ and SENTEMPQ have been added for pressure and
temperature sensor signals in order to control alarm and lockout signals. Whenever
there is no sensor, the quality of the binary input will be low. If sensor quality is low,
then lockout and alarm signals will get reset.
IEC 61850
identification
SSIMG
© Copyright 2017 Hitachi Power Grids. All rights reserved
Selected
Comment
value
0.00
Typically no additional filtering is required
25%
Set minimum voltage level to 25%
3
Set minimum current level to 3%
15,65
Set generator rated phase-to-phase voltage
3690
Set generator rated current
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
63
1MRK 511 407-UUS Rev. J
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v4
GUID-7F31EFA5-F8D8-4D8D-85DA-3418F70ABE94 v1
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v5
GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v6
Phasor measurement unit RES670
Application manual