Monitoring
Binary signals: Use only relevant signals to start the recording that is, protection trip, carrier
receive and/or pickup signals.
Analog signals: The level triggering should be used with great care, since unfortunate settings
will cause enormously number of recordings. If nevertheless analog input triggering is used,
chose settings by a sufficient margin from normal operation values. Phase voltages are not
recommended for trigging.
Remember that values of parameters set elsewhere are linked to the information on a report. Such
parameters are, for example, station and object identifiers, CT and VT ratios.
16.7
Logical signal status report BINSTATREP
16.7.1
Identification
Function description
Logical signal status report
16.7.2
Application
The Logical signal status report (BINSTATREP) function makes it possible to poll signals from
various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs and can be read
from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 97: BINSTATREP logical diagram
16.7.3
Setting guidelines
The pulse time
can be set or reset individually, but the pulse time will be the same for all outputs in the entire
BINSTATREP function.
264
There is a risk of flash wear out if the disturbance report triggers too often.
IEC 61850
identification
BINSTATREP
t
t is the only setting for the Logical signal status report (BINSTATREP). Each output
© Copyright 2017 Hitachi Power Grids. All rights reserved
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
t
IEC09000732-1-en.vsd
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
Phasor measurement unit RES670
1MRK 511 407-UUS Rev. J
GUID-F9D225B1-68F7-4D15-AA89-C9211B450D19 v3
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion res670 a20Relion res670 b20

Table of Contents