1MRK 511 407-UUS Rev. J
16.2.4
Setting guidelines
The parameters for Gas medium supervision SSIMG can be set via local HMI or Protection and
Control Manager PCM600.
Operation : This is used to disable/enable the operation of gas medium supervision i.e. Off/On.
PresAlmLimit : This is used to set the limit for a pressure alarm condition in the circuit breaker.
PresLOLimit : This is used to set the limit for a pressure lockout condition in the circuit breaker.
TempAlarmLimit : This is used to set the limit for a temperature alarm condition in the circuit
breaker.
TempLOLimit : This is used to set the limit for a temperature lockout condition in the circuit
breaker.
tPressureAlarm : This is used to set the time delay for a pressure alarm indication, given in s.
tPressureLO : This is used to set the time delay for a pressure lockout indication, given in s.
tTempAlarm : This is used to set the time delay for a temperature alarm indication, given in s.
tTempLockOut : This is used to set the time delay for a temperature lockout indication, given in s.
tResetPressAlm : This is used for the pressure alarm indication to reset after a set time delay in s.
tResetPressLO : This is used for the pressure lockout indication to reset after a set time delay in s.
tResetTempLO : This is used for the temperature lockout indication to reset after a set time delay
in s.
tResetTempAlm : This is used for the temperature alarm indication to reset after a set time delay in
s.
16.3
Liquid medium supervision SSIML (71)
16.3.1
Function revision history
Document
revision
A
B
C
D
E
Table continues on next page
Phasor measurement unit RES670
Application manual
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
© Copyright 2017 Hitachi Power Grids. All rights reserved
Section 16
Monitoring
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v3
GUID-37669E94-4830-4C96-8A67-09600F847F23 v4
GUID-751C8C78-891D-423B-825A-0774D0B6C658 v1
251

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion res670 a20Relion res670 b20

Table of Contents