ABB Relion 670 Series Applications Manual page 339

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 407-UUS Rev. J
When the setting of the DataObject Mod is changed at this level, all Logical Nodes inside the
logical device update their own behavior according to IEC61850-7-4. The supported values of the
function block TESTMODE are described in
When the function block TESTMODE is in test mode the Start LED on the LHMI is turned on with
steady light.
The parameter
Function test modes/Communication/Station Communication
The parameter Mod can be set on the LHMI to the same values as for the DataObject Mod of the
Root LD.LNN0 to
test modes/ Differential protection/GeneratorDiff(87G,3Id/I>)/ GENPDIF(87G,3Id/I>):1.
It is possible that the behavior of the function block TESTMODE is also influenced by other sources
as well, independent of the mode communicated via the IEC61850-8-1 station bus. For example the
insertion of the test handle into the test switch with its auxiliary contact is connected to a BI on
the IED and further inside the configuration to the input IED_TEST on the function block
TESTMODE. Another example is when loss of Service Values appears, or as explained above the
setting via the LHMI.
When setting via PST or LHMI the parameter
function is not executed and the behavior (beh) is set to
When a behavior of a function is
current state.
The IEC 61850-7-4 gives a detailed overview over all aspects of the test mode and other states of
mode and behavior. The status of a function block behavior
Main menu/Test/Function status/Function group/Function block descriptive name/LN name/
Outputs.
When the
control commands with a test bit are accepted.
When the
are accepted. Outputs to the process via a non-IEC 61850 link data are blocked by the function
block. Only process-related outputs on function blocks related to primary equipment are
blocked. If there is an XCBR function block used, the outputs
blocked.
When the
accepted. Outputs to the process via a non-IEC 61850 link data are blocked by the function
block. In addition, the function block can be blocked when their
done if the function block has a block input.
The block status of a component is shown on the LHMI as the
Beh: Main menu/Test/Function status/Function group/Function block descriptive name/LN
for
name/Outputs. If the
22.12.2
Setting guidelines
Remember always that there are two possible ways to place the IED in the
state. If, the IED is set to normal operation (
Phasor measurement unit RES670
Application manual
Mod of any specific function block can be configured under Main menu/Test/
On , Off , TestBlocked , Test or Blocked . For Example, Main menu/ Test/ Function
Off the function will not execute. The related Mod keeps its
When IEC 61850 Mod of a function is set to
LHMI will be set to flashing to indicate the abnormal operation of the IED.
Beh of a function block is set to Test , the function block is not blocked and all
Beh of a function block is set to Test/blocked , all control commands with a test bit
Beh of a function block is set to Blocked , all control commands with a test bit are
Blk output is not shown, the component cannot be blocked.
© Copyright 2017 Hitachi Power Grids. All rights reserved
Communication protocol manual, IEC 61850 Edition 2 .
Operation of any function in an IED is set to Off , the
Off and it is not possible to override it.
Off or Blocked , the Start LED on the
Beh is shown on the LHMI under the
EXC_Open and EXC_Close are
Blk output under the same path as
TestMode = Disabled ), but the functions are still
Section 22
Basic IED functions
Beh is blocked . This can be
TestMode = Enabled "
M15260-3 v7
333