1MRK 511 407-UUS Rev. J
A
CT 800/1
Star Connected
Protected Object
ANSI06000644 V3 EN-US
Figure 14: Wye connected three-phase CT set with its wye point away from the protected object and the
residual/neutral current connected to the IED
Where:
1)
2)
3)
4)
Table continues on next page
Phasor measurement unit RES670
Application manual
B
C
I_N
I_C
I_B
I_A
Shows how to connect three individual phase currents from a wye connected three-phase CT set to the
three CT inputs of the IED.
Shows how to connect residual/neutral current from the three-phase CT set to the fourth input in the
IED. It shall be noted that if this connection is not made, the IED will still calculate this current internally
by vectorial summation of the three individual phase currents.
Is the TRM where these current inputs are located. It shall be noted that for all these current inputs the
following setting values shall be entered.
•
CTprim =800A
•
CTsec =1A
CTStarPoint =FromObject
•
ConnectionType =Ph-N
•
The ratio of the first two parameters is only used inside the IED. The third parameter as set in this
example will have no influence on measured currents (that is, currents are already measured towards the
protected object).
Are three connections made in the Signal Matrix tool (SMT) and Application configuration tool (ACT),
which connects these three current inputs to the first three input channels on the preprocessing
function block 6). Depending on the type of functions, which need this current information, more than
one preprocessing block might be connected in parallel to these three CT inputs.
© Copyright 2017 Hitachi Power Grids. All rights reserved
IED
3
1
4
2
Analog inputs
6
SMAI2
BLOCK
AI3P
REVROT
AI1
^GRP2_A
AI2
^GRP2_B
AI3
^GRP2_C
AI4
^GRP2_N
AIN
5
ANSI06000644-3-en.vsdx
Section 4
59