Directional residual overcurrent
protection, four steps
8.2.3
Setting guidelines
The parameters for the four step residual over-current protection are set via the local HMI or
PCM600. The following settings can be done for the function.
Common base IED values for the primary current (
SBase ) are set in global base values for settings function GBASVAL.
power (
GlobalBaseSel : Selects the global base value group used by the function to define IBase , VBase and
SBase . Note that this function will only use IBase value.
SeqTypeUPol : This is used to select the type of voltage polarising quantity (that is, Zero seq or
Neg seq for direction detection).
SeqTypeIPol : This is used to select the type of current polarising quantity (that is, Zero seq or Neg
seq for direction detection).
Phasor measurement unit RES670
Application manual
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
Technical data table updated with note "Operate time and reset time are only valid if
harmonic blocking is turned off for a step".
2.2.3
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
The phase selection logic is added to allow phase segregated trip. The new phase
selections outputs added to this release are PHSELL1, PHSELL2 and PHSELL3. The
setting
EnPhaseSel is added to enable or disable phase selection. The maximum value
changed to 2000.0 % of IBase for
IEC 61850
identification
EF4PTOC
When inverse time over-current characteristic is selected, the trip time of the stage
will be the sum of the inverse time delay and the set definite time delay. Thus, if
only the inverse time delay is required, it is important to set the definite time delay
for that stage to zero.
© Copyright 2017 Hitachi Power Grids. All rights reserved
IMin1, IMin2, IMin3 and IMin4 settings.
IEC 60617
ANSI/IEEE C37.2
identification
device number
51N_67N
4(IN>)
4
alt
4
TEF-REVA V2 EN-US
IBase ), primary voltage ( VBase ) and primary
Section 8
Current protection
GUID-0F9199B0-3F86-45E0-AFC2-747052A20AE1 v1
M14881-1 v7
IP14988-1 v1
M15282-3 v13