ABB Relion 670 Series Applications Manual page 150

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 8
Current protection
=
3I
0
2 Z
EQUATION2023-ANSI V1 EN-US
Where
V
phase
Z
1
Z
0
R
f
The residual voltages in stations A and B can be written:
=
V
3I (Z
0 A
EQUATION2024-ANSI V1 EN-US
=
V
3I (Z
OB
EQUATION2025-ANSI V1 EN-US
The residual power, measured by the sensitive ground fault protections in A and B will be:
=
S
3V
0A
EQUATION2026-ANSI V1 EN-US
=
S
3V
0B
EQUATION2027-ANSI V1 EN-US
The residual power is a complex quantity. The protection will have a maximum sensitivity in the
characteristic angle RCA. The apparent residual power component in the characteristic angle,
measured by the protection, can be written:
S
0 A ,prot
EQUATION2028-ANSI V1 EN-US
=
S
0 B,prot
EQUATION2029-ANSI V1 EN-US
The angles φ
the station compensated with the characteristic angle RCA.
The protection will use the power components in the characteristic angle direction for
measurement, and as base for the inverse time delay.
144
3V
phase
×
+
+ ×
Z
3 R
1
0
f
is the phase voltage in the fault point before the fault
is the total positive sequence impedance to the fault point. Z
is the total zero sequence impedance to the fault point. Z
is the fault resistance.
×
+
3R )
0
T ,0
N
×
+
+
3R
Z
0
T ,0
N
lineAB,0
×
3I
0A
0
×
3I
0B
0
=
×
×
j
3V
3I cos
0 A
0
A
×
×
j
3V
3I cos
0 B
0
B
and φ
are the phase angles between the residual current and the residual voltage in
A
B
© Copyright 2017 Hitachi Power Grids. All rights reserved
= Z
0
)
1MRK 511 407-UUS Rev. J
= Z
+Z
+Z
+Z
1
sc
T,1
lineAB,1
lineBC,1
+3R
+Z
+Z
T,0
N
lineAB,0
lineBC,0
Phasor measurement unit RES670
Application manual
(Equation 48)
(Equation 49)
(Equation 50)
(Equation 51)
(Equation 52)
(Equation 53)
(Equation 54)