ABB Relion 670 Series Applications Manual page 74

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 4
Analog inputs
kV
13.8
V
120
ANSI06000600 V3 EN-US
Figure 21:
A Two phase-to-phase connected VT
Where:
1)
2)
Table continues on next page
68
A
B
C
kV
13.8
V
120
shows how to connect the secondary side of a phase-to-phase VT to the VT inputs on the IED
is the TRM where these three voltage inputs are located. It shall be noted that for these three voltage
inputs the following setting values shall be entered:
VTprim =13.8 kV
VTsec =120 V
Please note that inside the IED only ratio of these two parameters is used.