ABB Relion 670 Series Applications Manual page 145

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 407-UUS Rev. J
ANSI10000031 V1 EN-US
Figure 63: Relay characteristic angle given in degree
In a transmission network a normal value of RCA is about 80°.
VPolMin : Minimum polarization (reference) voltage % of VBase .
I>Dir : Operate residual current level for directional comparison scheme. The setting is given in %
IBase . The pickup forward or pickup reverse signals can be used in a communication scheme.
of
The appropriate signal must be configured to the communication scheme block.
8.4
Sensitive directional residual overcurrent and power
protection SDEPSDE (67N)
8.4.1
Identification
Function description
Sensitive directional residual over
current and power protection
Phasor measurement unit RES670
Application manual
Reverse
Area
AngleRCA
Iop = I2
© Copyright 2017 Hitachi Power Grids. All rights reserved
Forward
Area
ANSI10000031-1-en.vsd
IEC 61850
IEC 60617
identification
identification
SDEPSDE
-
Current protection
Vpol=-V2
ANSI/IEEE C37.2
device number
67N
Section 8
SEMOD171436-1 v4
SEMOD172025-2 v4
139