Section 11
Multipurpose protection
Set value for parameter
"VoltageInput"
UnbalancePh
9
10
PhaseA - PhaseB
11
PhaseB - PhaseC
12
PhaseC - PhaseC
13
MaxPh-Ph
MinPh-Ph
14
UnbalancePh-Ph
15
Note that the voltage selection from table
connections. The three-phase VT inputs can be connected to IED as either three phase-to-ground
voltages, VA, VB and VC or three phase-to-phase voltages V
actual VT connection is entered as a setting parameter for the pre-processing block, which will
then be taken care automatically.
11.1.2.2
Base quantities for CVGAPC function
The parameter settings for the base quantities, which represent the base (100%) for pickup levels
of all measuring stages shall be entered as setting parameters for every CVGAPC function.
Base current shall be entered as:
1.
rated phase-to-earth current of the protected object in primary amperes, when the measured
Current Quantity is selected from 1 to 9, as shown in table 20.
2.
rated phase current of the protected object in primary amperes multiplied by √3 (1.732 x
Iphase), when the measured Current Quantity is selected from 10 to 15, as shown in table 20.
Base voltage shall be entered as:
1.
rated phase-to-ground voltage of the protected object in primary kV, when the measured
Voltage Quantity is selected from 1 to 9, as shown in table 21.
2.
rated phase-to-phase voltage of the protected object in primary kV, when the measured
Voltage Quantity is selected from 10 to 15, as shown in table 21.
11.1.2.3
Application possibilities
Due to its flexibility the general current and voltage protection (CVGAPC) function can be used,
with appropriate settings and configuration in many different applications. Some of possible
examples are given below:
182
Comment
CVGAPC function will measure magnitude of unbalance voltage, which is
internally calculated as the algebraic magnitude difference between the
voltage phasor of the phase with maximum magnitude and voltage phasor of
the phase with minimum magnitude. Phase angle will be set to 0° all the time
CVGAPC function will measure the voltage phasor internally calculated as the
vector difference between the phase A voltage phasor and phase B voltage
phasor (VA-VB)
CVGAPC function will measure the voltage phasor internally calculated as the
vector difference between the phase B voltage phasor and phase C voltage
phasor (VB-VC)
CVGAPC function will measure the voltage phasor internally calculated as the
vector difference between the phase C voltage phasor and phase A voltage
phasor (VC-VA)
CVGAPC function will measure ph-ph voltage phasor with the maximum
magnitude
CVGAPC function will measure ph-ph voltage phasor with the minimum
magnitude
CVGAPC function will measure magnitude of unbalance voltage, which is
internally calculated as the algebraic magnitude difference between the ph-ph
voltage phasor with maximum magnitude and ph-ph voltage phasor with
minimum magnitude. Phase angle will be set to 0° all the time
© Copyright 2017 Hitachi Power Grids. All rights reserved
21
is always applicable regardless the actual external VT
, V
and V
AB
BC
1MRK 511 407-UUS Rev. J
. This information about
CA
SEMOD53443-112 v4
SEMOD53443-136 v3
Phasor measurement unit RES670
Application manual