ABB Relion 670 Series Applications Manual page 60

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 4
Analog inputs
ANSI06000196 V1 EN-US
Figure 10: Example how to set CT_WyePoint parameters in the IED
For busbar protection, it is possible to set the
The first solution will be to use busbar as a reference object. In that case for all CT inputs marked
with 1 in Figure 10, set
CT_WyePoint = FromObject .
set
The second solution will be to use all connected bays as reference objects. In that case for all CT
inputs marked with 1 in Figure 10, set
with 2 in Figure 10, set
Regardless which one of the above two options is selected, busbar differential protection will
behave correctly.
The main CT ratios must also be set. This is done by setting the two parameters
for each current channel. For a 1000/5 A CT, the following settings shall be used:
54
CT_WyePoint = ToObject , and for all CT inputs marked with 2 in Figure 10,
CT_WyePoint = FromObject , and for all CT inputs marked
CT_WyePoint = ToObject .
© Copyright 2017 Hitachi Power Grids. All rights reserved
Busbar
Busbar
Protection
1
2
CT_WyePoint parameters in two ways.
1MRK 511 407-UUS Rev. J
2
1
en06000196_ansi.vsd
CTsec and CTprim
Phasor measurement unit RES670