Section 19
Station communication
Hardware and software modules
The hardware needed for applying LON communication depends on the application, but one very
central unit needed is the LON Star Coupler and optical fibers connecting the star coupler to the
IEDs. To interface the IEDs from the MicroSCADA with Classic Monitor, application library LIB520 is
required.
The HV Control 670 software module is included in the LIB520 high-voltage process package,
which is a part of the Application Software Library in MicroSCADA applications.
The HV Control 670 software module is used for control functions in the IEDs. The module
contains a process picture, dialogues and a tool to generate a process database for the control
application in MicroSCADA.
When using MicroSCADA Monitor Pro instead of the Classic Monitor, SA LIB is used together with
670 series Object Type files.
Use the LON Network Tool (LNT) to set the LON communication. This is a software tool applied as
one node on the LON bus. To communicate via LON, the IEDs need to know
The node addresses of the other connected IEDs.
The network variable selectors to be used.
This is organized by LNT.
The node address is transferred to LNT via the local HMI by setting the parameter
Yes . The node address is sent to LNT via the LON bus, or LNT can scan the network for new nodes.
The communication speed of the LON bus is set to the default of 1.25 Mbit/s. This can be changed
by LNT.
19.4.2
MULTICMDRCV and MULTICMDSND
19.4.2.1
Identification
Function description
Multiple command and receive
Multiple command and send
19.4.2.2
Application
The IED provides two function blocks enabling several IEDs to send and receive signals via the
interbay bus. The sending function block, MULTICMDSND, takes 16 binary inputs. LON enables
these to be transmitted to the equivalent receiving function block, MULTICMDRCV, which has 16
binary outputs.
296
The HV Control 670 software module and 670 series Object Type files are used with
both 650 and 670 series IEDs.
IEC 61850
identification
MULTICMDRCV
MULTICMDSND
© Copyright 2017 Hitachi Power Grids. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
-
-
Phasor measurement unit RES670
1MRK 511 407-UUS Rev. J
M14804-35 v5
ServicePinMsg =
SEMOD119881-1 v3
GUID-1A6E066C-6399-4D37-8CA5-3074537E48B2 v3
M14790-3 v5
Application manual