Section 7
Impedance protection
example a stable case with synchronism retained), the function is as well reset, which includes
the pickup output signal (PICKUP), which is reset to 0 (FALSE) after
elapsed. However, the measurements of analogue quantities such as R, X, P, Q, and so on
continue without interruptions. Recommended setting of
seconds.
NoOfSlipsZ1 : Maximum number of pole slips with centre of electromechanical oscillation
within zone 1 required for a trip. Usually,
NoOfSlipsZ2 : Maximum number of pole slips with centre of electromechanical oscillation
within zone 2 required for a trip. The reason for the existence of two zones of operation is
selectivity, required particularly for successful islanding. If there are several pole slip (out-of-
step) relays in the power system, then selectivity between relays is obtained by the relay reach
(for example zone 1) rather then by time grading. In a system, as in Table 12, the number of
allowed pole slips in zone 2 can be the same as in zone 1. Recommended value:
2 or 3 .
Operation : With the setting Operation OOSPPAM function can be set On/Off .
OperationZ1 : Operation zone 1 Enabled , Disabled . If OperationZ1 = Disabled , all pole-slips with
centre of the electromagnetic oscillation within zone 1 are ignored. Default setting =
More likely to be used is the option to extend zone 1 so that zone 1 even covers zone 2. This
feature is activated by the input to extend the zone 1 (EXTZ1).
OperationZ2 : Operation zone 2 Enabled , Disabled . If OperationZ1 = Disabled , all pole-slips with
centre of the electromagnetic oscillation within zone 2 are ignored. Default setting =
tBreaker : Circuit breaker opening time. Use the default value tBreaker = 0.000 s if unknown. If
the value is known, then a value higher than 0.000 is specified, for example
the out-of-step function gives a trip command approximately 0.040 seconds before the
currents reach their minimum value. This in order to decrease the stress imposed to the
circuit breaker.
VBase : This is the voltage at the point where the Out-of-step protection is installed. If the
protection is installed on the generator output terminals, then
phase to phase voltage of the protected generator. All the resistances and reactances are
measured and displayed referred to voltage
ReverseR , and ForwardR must be given referred to VBase. IBase is the protected generator
nominal (rated) current, if the Out-of-step protection belongs to a generator protection
scheme.
InvertCTCurr : If the currents fed to the Out-of-step protection are measured on the protected
generator neutral side (LV-side) then inversion is not necessary (
provided that the CT's orientation complies with ABB recommendations, as shown in Table 12.
If the currents fed to the Out-of-step protection are measured on the protected generator
output terminals side (HV-side), then invertion is necessary (
provided that the CT's actual direction complies with ABB recommendations, as shown in
Table 12.
116
© Copyright 2017 Hitachi Power Grids. All rights reserved
tReset is in the range of 6 to 12
NoOfSlipsZ1 = 1 .
VBase is the nominal (rated)
VBase . Observe that ReverseX , ForwardX ,
InvertCTCurr = Enabled ),
1MRK 511 407-UUS Rev. J
tReset interval of time has
NoOfSlipsZ2 =
Enabled .
Enabled .
tBreaker = 0.040 s :
InvertCTCurr = Disabled ),
Phasor measurement unit RES670
Application manual