Identification
Function description
Directional underpower protection
8.6.2
Application
The task of a generator in a power plant is to convert mechanical energy available as a torque on a
rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that it does not
cover bearing losses and ventilation losses. Then, the synchronous generator becomes a
synchronous motor and starts to take electric power from the rest of the power system. This
operating state, where individual synchronous machines operate as motors, implies no risk for the
machine itself. If the generator under consideration is very large and if it consumes lots of electric
power, it may be desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous state. The task of
the reverse power protection is to protect the turbine and not to protect the generator itself.
Steam turbines easily become overheated if the steam flow becomes too low or if the steam
ceases to flow through the turbine. Therefore, turbo-generators should have reverse power
protection. There are several contingencies that may cause reverse power: break of a main steam
pipe, damage to one or more blades in the steam turbine or inadvertent closing of the main stop
valves. In the last case, it is highly desirable to have a reliable reverse power protection. It may
prevent damage to an otherwise undamaged plant.
During the routine shutdown of many thermal power units, the reverse power protection gives the
tripping impulse to the generator breaker (the unit breaker). By doing so, one prevents the
disconnection of the unit before the mechanical power has become zero. Earlier disconnection
would cause an acceleration of the turbine generator at all routine shutdowns. This should have
caused overspeed and high centrifugal stresses.
When the steam ceases to flow through a turbine, the cooling of the turbine blades will disappear.
Now, it is not possible to remove all heat generated by the windage losses. Instead, the heat will
increase the temperature in the steam turbine and especially of the blades. When a steam turbine
rotates without steam supply, the electric power consumption will be about 2% of rated power.
Even if the turbine rotates in vacuum, it will soon become overheated and damaged. The turbine
overheats within minutes if the turbine loses the vacuum.
The critical time to overheating a steam turbine varies from about 0.5 to 30 minutes depending on
the type of turbine. A high-pressure turbine with small and thin blades will become overheated
more easily than a low-pressure turbine with long and heavy blades. The conditions vary from
turbine to turbine and it is necessary to ask the turbine manufacturer in each case.
Power to the power plant auxiliaries may come from a station service transformer connected to
the secondary side of the step-up transformer. Power may also come from a start-up service
transformer connected to the external network. One has to design the reverse power protection
so that it can detect reverse power independent of the flow of power to the power plant
auxiliaries.
Phasor measurement unit RES670
Application manual
IEC 61850
identification
GUPPDUP
© Copyright 2017 Hitachi Power Grids. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
37
P <
2
SYMBOL-LL V2 EN-US
Section 8
Current protection
SEMOD158941-2 v4
SEMOD151283-4 v5