ABB Relion 670 Series Applications Manual page 101

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 407-UUS Rev. J
Rule 3:
This rule is only related to the connection of 3PHSUM block to the PHASORREPORT block. If
3PHSUM block is configured to use external DFT reference (from SMAI reference block), it shall
only be connected to the same PHASORREPORT block instance as the one the SMAI reference
block is connected to. In other words, both the SMAI reference block and 3PHSUM block (3PHSUM
block with external DFT reference) shall be connected to the same instance of PHASORREPORT
block (PHASOR1-32 of Instance number 1 or 2).
Figure
42
where SMAI3 is configured as the reference block for DFT reference external out (DFTRefExtOut)
and 3PHSUM uses external DFT reference (from SMAI3). Figures
setting parameters.
IEC140000129 V2 EN-US
Figure 42: An example of correct connection of 3PHSUM and PHASORREPORT blocks in ACT
IEC140000130 V1 EN-US
Figure 43: SMAI1 setting parameters example-showing that SMAI3 is selected as the DFT
Phasor measurement unit RES670
Application manual
shows an example of correct connection of 3PHSUM and PHASORREPORT blocks in ACT
reference (DFTRefGrp3)
© Copyright 2017 Hitachi Power Grids. All rights reserved
Wide area measurement system
43
and
44
show the corresponding
IEC140000129-2-en.vsd
IEC140000130-1-en.vsd
Section 6
95