YASKAWA HV600 Installation & Startup page 258

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

7.16 U: Monitors
No.
Name
(Hex.)
U4-22
Modbus CmdData (hex)
(07DE)
U4-23
Option CmdData (hex)
(07DF)
U4-24
Number of Runs (Low)
(07E6)
U4-25
Number of Runs(High)
(07E7)
U4-61
Total EMOVR Run Time
(3096)
Expert
U5: PID Monitors
No.
Name
(Hex.)
U5-01
PID Feedback
(0057)
U5-02
PID Input
(0063)
258
Shows the operation signal (register 0001H) sent to the drive from MEMOBUS/Modbus
communications as a 4-digit hexadecimal number (zero suppress). The keypad shows the operation
signal as specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Not used (normal value of 0).
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
Shows the operation signal (register 0001H) sent to the drive from MEMOBUS/Modbus
communications as a 4-digit hexadecimal number. The keypad shows the operation signal as
specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Not used (normal value of 0).
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
Shows the lower 4 digits of the drive run count.
Note:
The drive run count is an 8-digit number. Monitor U4-25 [Number of Runs(High)] shows the
upper 4 digits and U4-24 shows the lower 4 digits.
Shows the lower 4 digits of the drive run count.
Note:
The drive run count is an 8-digit number. Monitor U4-25 shows the upper 4 digits and U4-24
[Number of Runs (Low)] shows the lower 4 digits.
Shows the length of time that the drive operated in Emergency Override Mode.
Unit: 1 min
Note:
• The maximum value is 60,000 min.
• This monitor does not accumulate operation time when S6-07 = 1 [EMOVR Fault Suppression
Mode = Test Mode].
Shows the PID control feedback value.
Unit: 0.01%
Note:
Parameters b5-46 [PID Unit Display Selection], b5-38 [PID User Unit Display Scaling], and b5-
39 [PID User Unit Display Digits] set the unit, range, and resolution.
Shows the change between the PID setpoint and PID feedback (the quantity of PID input) as a
percentage of the maximum output frequency.
Unit: 0.01%
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Description
Description
MFAO Signal Level
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
MFAO Signal Level
10 V = Maximum frequency
(-10 V to +10 V)
10 V: Maximum frequency
(0 V to +10 V)