YASKAWA HV600 Installation & Startup page 134

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

5.6 Minor Faults/Alarms
Code
Name
EF0
Option Card External Fault
Note:
• The drive detects this error if the alarm function on the external device side is operating.
• If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
• Use F6-03 [Comm External Fault (EF0) Select] to set the stopping method for this fault.
Code
Name
EF1
External Fault (Terminal S1)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
EF2
External Fault (Terminal S2)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
EF3
External Fault (Terminal S3)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
EF4
External Fault (Terminal S4)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
EF5
External Fault (Terminal S5)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
EF6
External Fault (Terminal S6)
134
Causes
The communication option card received an external
fault from the controller.
Programming error occurred on the controller side.
Causes
MFDI terminal S1 caused an external fault through an
external device.
The wiring is incorrect.
External Fault [H1-01 = 2C to 2F] is set to MFDI
terminal S1, but the terminal is not in use.
Causes
MFDI terminal S2 caused an external fault through an
external device.
The wiring is incorrect.
External Fault [H1-02 = 2C to 2F] is set to MFDI
terminal S2, but the terminal is not in use.
Causes
MFDI terminal S3 caused an external fault through an
external device.
The wiring is incorrect.
External Fault [H1-03 = 2C to 2F] is set to MFDI
terminal S3, but the terminal is not in use.
Causes
MFDI terminal S4 caused an external fault through an
external device.
The wiring is incorrect.
External Fault [H1-04 = 2C to 2F] is set to MFDI
terminal S4, but the terminal is not in use.
Causes
MFDI terminal S5 caused an external fault through an
external device.
The wiring is incorrect.
External Fault [H1-05 = 2C to 2F] is set to MFDI
terminal S5, but the terminal is not in use.
Causes
MFDI terminal S6 caused an external fault through an
external device.
The wiring is incorrect.
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input from the controller.
Examine the operation of the controller program.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal S1.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal S2.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal S3.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal S4.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal S5.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal S6.