YASKAWA HV600 Installation & Startup page 187

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

d4: Frequency Ref Up/Down & Hold
No.
Name
(Hex.)
d4-01
Freq Reference Hold
Selection
(0298)
d4-10
Up/Down Freq Lower Limit
Select
(02B6)
d6: Field Weakening
No.
Name
(Hex.)
d6-01
Field Weakening Level
(02A0)
d6-02
Field Weakening Frequency
Limit
(02A1)
d7: Offset Frequency
No.
Name
(Hex.)
d7-01
Offset Frequency 1
(02B2)
RUN
d7-02
Offset Frequency 2
(02B3)
RUN
d7-03
Offset Frequency 3
(02B4)
RUN
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Sets the function that saves the frequency reference after a Stop command or when de-energizing the
drive.
Set H1-xx [MFDI Function Selection] to one of these values to enable this parameter:
• A [Accel/Decel Ramp Hold]
• 10/11 [Up/Down Command]
0 : Disabled
1 : Enabled
Sets the lower frequency limit for the Up/Down function.
0 : Greater of d2-02 or Analog
1 : d2-02
Sets the drive output voltage as a percentage of E1-05 [Maximum Output Voltage] when H1-xx = 63
[Field Weakening] is activated.
Sets the minimum output frequency to start field weakening.
Uses H1-xx = 44 [MFDI Function Select = Add Offset Frequency 1 (d7-01)] as a percentage of the
Maximum Output Frequency to add or subtract the set frequency to/from the frequency reference.
Uses H1-xx = 45 [MFDI Function Select = Add Offset Frequency 2 (d7-02)] as a percentage of the
Maximum Output Frequency to add or subtract the set frequency to/from the frequency reference.
Uses H1-xx = 46 [MFDI Function Select = Add Offset Frequency 3 (d7-03)] as a percentage of the
Maximum Output Frequency to add or subtract the set frequency to/from the frequency reference.
Description
Description
Description
7.5 d: Reference Settings
Default
(Range)
0
(0, 1)
0
(0, 1)
Default
(Range)
80%
(0 - 100%)
0.0 Hz
(0.0 - 400.0 Hz)
Default
(Range)
0.0%
(-100.0 - +100.0%)
0.0%
(-100.0 - +100.0%)
0.0%
(-100.0 - +100.0%)
187
7

Hide quick links:

Advertisement

Table of Contents
loading