YASKAWA HV600 Installation & Startup page 252

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

7.16 U: Monitors
No.
Name
(Hex.)
U2-05
Output Current@Fault
(0084)
U2-07
Output Voltage@Fault
(0086)
U2-08
DC Bus Voltage@Fault
(0087)
U2-09
Output Power @ Fault
(0088)
U2-11
Byp Inp Terminal Status @
Fault
(008A)
U2-12
Byp Relay Status @ Fault
(008B)
U2-13
Bypass Status @ Fault
(008C)
U2-14
Elapsed Time @ Fault
(008D)
U2-15
SFS Output @ Fault
(07E0)
U2-16
q-Axis Current@Fault
(07E1)
252
Shows the output current at the fault that occurred most recently.
Use U1-03 [Output Current] to monitor the output current. The keypad shows the value of U1-03 in
amperes (A).
When you use serial communications to show the monitor, the current is "8192 = drive rated current
(A)". Use the formula: "Numerals being displayed / 8192 × drive rated current (A)" to use the serial
communication current value shown in the monitor.
Unit: Determined by the drive model.
• 0.01 A: 2011 to 2046, 4005 to 4014
• 0.1 A: 2059 to 2273, 4021 to 4302
Shows the output voltage reference at the fault that occurred most recently.
Use U1-06 [Output Voltage Ref] to monitor the output voltage reference.
Unit: 0.1 V
Shows the DC bus voltage at the fault that occurred most recently.
Use U1-07 [DC Bus Voltage] to monitor the DC bus voltage.
Unit: 1 V
Shows the output power at the fault that occurred most recently.
Use U1-08 [Output Power] to monitor the output power.
Unit: 0.1 kW
Shows the status of the bypass digital input terminals at the most recent fault where 1 = (ON) and 0 =
(OFF).
For example, U2-11 shows "00000011" when terminals S1 and S2 are ON.
Use Ub-02 [Bypass Digital Input Status] to monitor the terminal status.
bit 0 : Terminal S1
bit 1 : Terminal S2
bit 2 : Terminal S3
bit 3 : Terminal S4
bit 4 : Terminal S5
bit 5 : Terminal S6
bit 6 : Terminal S7
bit 7 : Not used (normal value of 0).
Shows the status of the bypass digital output terminals at the most recent fault where 1 = (ON) and 0
= (OFF).
For example, U2-12 shows "00000011" when terminals M1 and M3 are ON.
Use Ub-02 [Bypass Digital Output Status] to monitor the terminal status.
bit 0 : Terminals M1-M2
bit 1 : Terminals M3-M4
bit 2 : Terminals M5-M6
bit 3 : Not used (normal value of 0).
bit 4 : Not used (normal value of 0).
bit 5 : Not used (normal value of 0).
bit 6 : Not used (normal value of 0).
bit 7 : Fault relay MA/MB-MC
Shows the status of the bypass at the most recent fault where 1 = (ON) and 0 = (OFF).
For example, U2-13 shows "00000001" during run.
Use Ub-05 [Bypass Status 1] to monitor the bypass.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive ready
bit6 : During minor fault detection
bit7 : During fault detection
Shows the cumulative operation time of the drive at the fault that occurred most recently.
Use U4-01 [Cumulative Ope Time] to monitor the cumulative operation time.
Unit: 1 h
Shows the output frequency after soft start at the fault that occurred most recently.
Use U1-16 [SFS Output Frequency] to monitor the output frequency after soft start.
Unit: 0.01 Hz
Shows the q-Axis current of the motor at the fault that occurred most recently.
Use U6-01 [Iq Secondary Current] to monitor the q-Axis current of the motor.
Unit: 0.1 %
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Description
MFAO Signal Level
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available